Safe and reliable: Metal armored and fully enclosed structure
Take the measures of balancing the electric field, prime conductor’s material is insulating heat shrinkable material with high insulation performance.
The low voltage chamber and each high voltage compartment are independently separated.
Quick opening and closing earth switch is used for grounding and has the ability to open or close short circuit current.
The operation of all equipment, including the opening and closing of circuit breakers, circuit breaker handcart push in or move out and the operation of opening and closing of the grounding switch, can be carried out on the condition of the door panel closed
With a reliable locking device, can effectively prevent the misoperation.
Looking through the front and rear observation windows of the door panel, it is convenient to check the opening and closing state of the circuit breaker and the position of the handcart, mechanism energy storage state, the opening and closing position of the grounding switch and the connection of the cable head.
The products meet IEC62271\GB/T3906 standards and China's electric power industry standard.
Strong practicality
Enclosure protection classification IP4X, to prevent dirt and small animals entering.
The vacuum circuit breaker is maintenance-free type, a little maintain is needed for its matched operating mechanism.
The interchangeability of handcart is good; it is very convenient to replace circuit breaker.
The secondary wire is laid in a generous groove, which is beautiful and easy to check.
Wide adaptability
Suitable for cable and busbar in and out or cable and busbar mixed in and out.
Suitable for all kinds of conventional cable head.
Can be connected by multiple cables
Serial number | Project | Unit | Parameters | |||
1 | Rated voltage | kV | 12 | 24 | ||
2 | Rated frequency | Hz | 50 | 50 | ||
3 | 1min Power frequency withstand voltage (effective value) | kV | Phase to phase | 42 | Phase to phase | 65 |
between open contacts | 48 | between open contacts | 79 | |||
Lightning shock resistance voltage (peak) | kV | Phase to phase | 75 | Phase to phase | 125 | |
between open contacts | 85 | between open contacts | 145 | |||
4 | Rated current | A | 630~2000 | 2500~4000 | 630~3150 | |
5 | Rated short circuit breaking current | kA | 25、31.5、40 | 31.5、40、50 | 25、31.5 | |
6 | Rated short circuit close current (peak) | kA | 63、80、100 | 80、100、125 | 63、80 | |
7 | Rated short-time withstand current (heat stable current 4S) | kA | 25、31.5、40 | 31.5、40、50 | 25、31.5 | |
8 | Rated peak withstand tolerance current (dynamic stability current) | kA | 63、80、100 | 800、100、125 | 63、80 | |
9 | Auxiliary control loop rated voltage | V | DC or AC:110/220 | |||
10 | Protection grade | IP41(Open the door between compartments is IP2X) | ||||
11 | Dimensions (width X depth X height) | mm | 800×1500×2300 | 1000×1860×2380 | ||
12 | Weight | Kg | 700~900 | 800~1500 |
KYN28-12/24 switch cabinet consists of two parts: cabinet body and removable parts (commonly known as handcart).
Cabinet and the metal partition are divided into several functional compartments, such as busbar room, cable room and low voltage room.
The removable parts of switch cabinet can be equipped with vacuum circuit breaker handcart, voltage mutual inductance handcart, arrester handcart, isolation handcart and fuse handcart, etc.